Chapter 13 Analog Input Module (XBF-AD04C)
(3) DC 1 ~ 5V Input range
Digital
Unsigned Value
(-192 ~ 16,191)
-192 0 4,000 8,000 12,000 16,000 16,191
Signed Value
(-8,192 ~ 8,191)
-8,192 -8,000 -4,000 0 4,000 8,000 8,191
Precise Value
(952 ~ 5,047)
952 1,000 2,000 3,000 4,000 5,000 5,047
Percentile Value
(-120 ~ 10,119)
-120 0 2,500 5,000 7,500 10,000 10,119
(4) DC 0 ~ 5V Input range
output range
Unsigned Value
(-192 ~ 16,191)
-192 0 4,000 8,000 12,000 16,000 16,191
Signed Value
(-8,192 ~ 8,191)
-8,192 -8,000 -4,000 0 4,000 8,000 8,191
Precise Value
(-60 ~ 5,059)
-60 0 1,250 2,500 3,750 5,000 5,059
Percentile Value
(-120 ~ 10,119)
-120 0 2,500 5,000 7,500 10,000 10,119
(5) DC 0 ~ 10V Input range
Digital
output range
Unsigned Value
(-192 ~ 16,191)
-192 0 4,000 8,000 12,000 16,000 16,191
Signed Value
(-8,192 ~ 8,191)
-8,192 -8,000 -4,000 0 4,000 8,000 8,191
Precise Value
(-120 ~ 10,119)
-120 0 2,500 5,000 7,500 10,000 10,119
Percentile Value
(-120 ~ 10,119)
-120 0 2,500 5,000 7,500 10,000 10,119
(6) DC -10 ~ 10V Input range
Digital
output range
Unsigned Value
(-192 ~ 16,191)
-192 0 4,000 8,000 12,000 16,000 16,191
Signed Value
(-8,192 ~ 8,191)
-8,192 -8,000 -4,000 0 4,000 8,000 8,191
Precise Value
(-10,240 ~ 10,239)
-10,240 -10,000 -5,000 0 5,000 10,000 10,239
Percentile Value
(-120 ~ 10,119)
-120 0 2,500 5,000 7,500 10,000 10,119
13 - 7