Chapter 13 Analog Input Module (XBF-AD04C)
 
 
13.6.3  Average processing 
 
1) 
Time average 
 
Input value of specified channel accumulates during setting time and then the average 
value of the sum is shown with digital data.   
평균처리후 입력값
실제 입력값
평균처리구간 샘플링처리구간
Channel scan Interval (1ms/ used channel)
Input value after 
average processing
Actual input value
Average processing interval
Average processing interval Sampling processing interval
 
Setting range = 4 ~ 16,000 [ms] 
In case of the time average, the average processing count is calculated by depending on 
the number of used channels. 
ms1 channels used ofNumber 
 timeAverage
count processing Average
×
=
   
 
2) 
Number of averages 
 
Input value of specified channel accumulates during setting numbers and then the average 
value of the sum is shown with digital data.   
평균처리후 입력값
실제 입력값
Average processing interval
평균처리구간 샘플링처리구간
Channel scan interval (1ms/ used channel)
Input value after 
average processing
Actual input value
Average processing interval
Average processing interval
Sampling processing interval
 
Setting range = 2 ~ 64,000 [times] 
In case of number of averages, the average processing interval is calculated by depending 
on used channels. 
 
Average processing interval [
]   
= Number of averages × Number of used channels × 1
 
 
 
 
 
 
 
 
13 - 11