XGB Analog edition manual 
 
 
2) Conversion characteristic of analog output module (XBF-DC04C: Current)   
 
Analog 
output 
value
0mA
5mA
10mA
15mA
20mA
20.24
4mA
8mA
12mA
16mA
20mA
20.192
3.808
Percentile value
Unsigned value
5000
0 8000 16000
Digital 
input value
P
r
a
c
t
i
c
a
l
 
r
a
n
g
e
 
o
 
 
 
Offset value
Gain value
Signed value
-8000
0
8000
10000
0
16191
8191
10119
-191
-8192
-120
 
 
 (1) DC 4 ~ 20
㎃  Output range 
Digital input range
㎃
Unsigned value 
(-192 ~ 16,191) 
-192  0  4,000  8,000  12,000  16,000  16,191 
Signed value 
(-8,192 ~ 8,191) 
-8,192  -8,000  -4,000  0  4,000  8,000  8,191 
Precise value 
(3,808 ~ 20,191) 
3,808  4,000  8,000  12,000  16,000  20,000  20,191 
Percentile value 
(-120 ~ 10,119) 
-120  0  2,500  5,000  7,500  10,000  10,119 
 
 (2) DC 0 ~ 20
㎃  Output range 
Digital input range
㎃
−
Unsigned value 
(-192 ~ 16,191) 
− 
0  4,000  8,000  12,000  16,000  16,191 
Signed value 
(-8,192 ~ 8,191) 
− 
-8,000  -4,000  0  4,000  8,000  8,191 
Precise value 
(0 ~ 20,239) 
− 
0  5,000  10,000  15,000  20,000  20,239 
Percentile value 
(-120 ~ 10,119) 
− 
0  2,500  5,000  7,500  10,000  10,119 
 
14 - 8