Chapter 2 Analog Input Module (XBF-AD04A) 
2 - 31 
 
 
2.12.2 Operation parameters setting area   
 
Setting area of A/D conversion module’s Run parameters is as described in Table. 
 
Memory address 
Details  R/W  Remark 
Hex.  Dec. 
0
H
 0 Channel enable/disable setting R/W PUT 
1
H
 1 
Setting ranges of input 
voltage/current 
R/W PUT 
2
H
  2  Output data format setting  R/W  PUT 
3
H
 3 
Filter processing enable/disable 
setting 
R/W PUT 
4
H
  4  CH0 filter constant 
R/W PUT 
5
H
  5  CH1 filter constant 
6
H
  6  CH2 filter constant 
7
H
  7  CH3 filter constant 
C
H
 12 
Average processing enable/disable 
setting 
R/W 
PUT 
D
H
  13  Average processing method setting R/W 
E
H
  14  CH0 average value 
R/W 
F
H
  15  CH1 average value 
10
H
  16  CH2 average value 
11
H
  17  CH3 average value 
16
H
 22  Error code  R/W GET 
※R/W is to denote Read/Write if available from PLC program. 
 
 
 
(1) Setting operation channels 
If the channel to use is not specified, all the channels will be set to prohibit. 
 
 
 
 
 
 
 
 
 
 
 
(2) Setting input range 
The range of analog voltage input is DC 0~10V, the range of analog current input is DC 4~20mA.   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8 bit7 bit6 bit5 bit4 bit3 bit2 bit1  bit0 
—  — — — ————————
CH.
3
CH. 
2
CH. 
1 
CH. 
0 
bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8 bit7 bit6 bit5 bit4 bit3 bit2 bit1  bit0 
—  — — — ———— CH.3 CH.2 CH.1 CH.0 
Setting channel to use (bit) 
            Bit On (1): Run, Bit Off (0): Stop
 
Address 0   
Setting input range (bit) 
 00: 0 ~ 10V(4 ~ 20mA) 
 01: 0 ~ 20mA 
 11: 4 ~ 20mA 
Address 1