Initial Adjustments
CAUTION
Read and understand the operation of the individual adjustments before attempting any initial adjustments.
Before starting the generator, the procedures in the following paragraphs should be performed.
Remove the 5 ampere fuse before starting the generator for the rst time. Perform all preliminary engine governor
adjustments without the regulator energized.
After initial governor adjustments are complete, reinstall the 5 ampere fuse and connect only the power input
leads or PMG leads to the regulator. Remove all other regulator connections that may be present and temporarily
insulate them.
40
3
Main Index
5
Section 5 Index
41
3
Main Index
5
Section 5 Index

Table of Contents