83
HEPA filter
This allows you to enable management of the HEPA filter, when included with the unit. By default, the dedicated
checkbox is not ticked.
When enabled, the days of use of the filter will be controlled. After 365 days (default value) a warning will be
displayed to call customer support and to replace the filter (chapter 2.6.1).
Internal Charcoal filter
This allows you to enable management of the Internal Charcoal filter, when included with the unit (chapter 5.5
or chapter 5.6). By default, the dedicated checkbox is not ticked.
When enabled, the hours of use of the filters will be controlled. After 360 hours (default value) a warning will
be displayed to call customer support and to replace the filters (chapter 2.6.1).
Air speed
In this section, you may set the maximum and minimum air speed pursuant to current standards. By default,
the maximum value is 1m/s, and the minimum 0.5m/s. These values can be edited by the Service, Admin and
basic users enabled to do so.
You may not set values lower than 0.3m/s or higher than 1m/s.