35
Module Settings
5.7.1 Jumper and connector
The alarm transmit signal to the PR-300 can be programmed to turn off when signal silence is
active. This allows the city tie box to be manually reset. On subsequent alarms the silenceable
signals will resound and the city tie box will be retriggered (see 9.0 System Configuration on
page 60).
The trouble transmit signal to the PR-300 can be programmed to delay AC power fail for zero,
1, 2, 3 hours if this is the only system trouble (see Chapter 9.0 System Configuration on
page 60).
The PR-300 does not require any display points.
P1 Cable to P2 of main fire alarm module.
JW4 Jumper on the main fire alarm module must be removed if a city tie module is
installed.