FX Series Programmable Controllers Execution Times And Instructional Hierarchy 7
7-10
Q1:
These instructions require NO preliminary contact devices such as LD, AND, OR etc.
Q2:
Where n is referred to this identifies the quantity of registers to be manipulated.
n can be equal or less than 512.
Q3:
Where n is referred to this identifies the quantity of bit devices to be manipulated.
n can be equal or less than selected operating mode, i.e. if 32 bit mode is selected then n can
have a value equal or less than 32.
Q4:
Where "n" is referred to this identifies the quantity of bit devices to be manipulated.
When an FX1N PLC is used "n" can be equal or less than 1536.
However, when an FX1S controller is used "n" can be equal or less than 512.
Q5:
Where "n" is referred to this identifies the quantity devices to be manipulated. "n" can have any value
taken from the range 2 through 512.
Q6:
Where "n" is referred to this identifies the range of devices to be reset. The device type being reset is
identified by the device letter in brackets in the '16/32 bit' column.
Q7:
Where "n" is referred to this identifies the number of devices the mean is to be calculated from. The
value of "n" can be taken from the range 1 through 64.
Q8:
Where "n" is referred to this identifies the range of devices to be refreshed. The value of "n" is always
specified in units of 8, i.e 8, 16, 24.....128. The maximum allowable range is dependent on the
number of available inputs/outputs.
Q9:
Where "n" is referred to this identifies the time setting for the input filters operation.
"n" can be selected from the range 0 through to 60 msec.
Q10:
There are limits to the total combined use of these instructions. For FX1S and FX1N there should be
no more than 4 simultaneously active instructions. However, FX
2N and FX2Nc can have 6
simultaneously active instructions.
Q11:
Where "n" is referred to this identifies the number of output points. "n" may have a value equal or less
than 64.
Q12:
Where "n" is referred to this identifies the number of words read or written FROM/TO the special
function blocks.
Q13:
Where "n" is referred to this identifies the number of octal (8 bit) words read or written when two FX
PLCs are involved in a parallel running function.
Q14:
Where "n" is referred to this identifies the number of elements in a stack, for 16 bit operation n has a
maximum of 256. However, for 32 bit operation n has a maximum of 128.
Q15:
Where "m1" is referred to this identifies the number of elements in the data table.
Values of m1 are taken from the range 1 to 32. For a the SORT instruction to completely process the
data table the SORT instruction will be processed m1 times.

Table of Contents

Other manuals for Mitsubishi FX1S Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX1S Series and is the answer not in the manual?

Mitsubishi FX1S Series Specifications

General IconGeneral
ModelFX1S Series
I/O Points10 to 30 points
Program Memory2000 steps
Power SupplyAC
CommunicationRS-422
ExpansionNo expansion
Programming LanguageLadder Logic
Input Voltage100-240V AC
Built-in High-Speed CounterUp to 60 kHz (single-phase)
WeightApprox. 0.3 kg
Dimensions90 x 60 x 75 mm

Related product manuals