FX Series Programmable Controllers Basic Program Instructions 2
2-21
2.18 Inverse
Program example:
Basic points to remember:
- The INV instruction is used to change (invert) the logical state of the current ladder
network at the inserted position.
- Usage is the same as for AND and ANI; see earlier.
Mnemonic Function Format Devices Program steps
INV
(Inverse)
Invert the current
result of the
internal PLC
operations
N/A 1
FX
1S
FX1N FX2N
FX2NC
X0
PLS M0
M0
SET Y0
X1
PLF M1
M1
RST Y0
0
0
0
1
1
1
0
LD
PLS
LD
SET
LD
RST
PLF
LD
0
1
4
5
8
9
6
3
0
X
M
M
M
Y
M
Y
X
Usages for INV
• Use the invert instruction to quickly change the logic of a complex circuit.
It is also useful as an inverse operation for the pulse contact instructions LDP, LDF,
ANP, etc.

Table of Contents

Other manuals for Mitsubishi FX1S Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX1S Series and is the answer not in the manual?

Mitsubishi FX1S Series Specifications

General IconGeneral
ModelFX1S Series
I/O Points10 to 30 points
Program Memory2000 steps
Power SupplyAC
CommunicationRS-422
ExpansionNo expansion
Programming LanguageLadder Logic
Input Voltage100-240V AC
Built-in High-Speed CounterUp to 60 kHz (single-phase)
WeightApprox. 0.3 kg