FX Series Positioning Controllers Troubleshooting 10
10-5
10.2.3 Error code list
Table 10.3: Error code list
Error
category
Error
code
Details Reset
Simultaneous
2-axis mode
Independent
2-axis mode
No error 0000 No error

System
parameter
1100
to
1111
If one of the parameters
100 to 111has been set
incorrectly, the corre-
sponding error code 1100
to 1111 is displayed.
Make sure that the
parameter setting
evaluated as error is
within the set range.
Global error Global error
Parameter
setting
errors
2000
to
2056
If one of the positioning
parameters 0 to 24 or the
I/O control parameters 30
to 56 is set incorrectly, the
corresponding error code
2000 to 2056 is displayed.
Local error Local error
Program
error
3000
Program No. does not
exist.
When the start command
is given in the AUTO
mode, the specified pro-
gram No. does not exist.
Change the pro-
gram No. or create
the program.
Global error Local error
3001
"m02(END)" is not pro-
vided in the program.
The m02 (END) command
is not provided at the end
of the specified program.
Add "m02 (END)" at
the end of the speci-
fied program.
3003
Set value register overflow
When the set value
exceeds 32 bits.
Change the set
value to the value of
32 bits or less.
Local error
Local error
3004
The set value is defective.
When you input the value
outside a set range.
Change the set value
to the value within
the range of setting.
3005
The imperative type is
defective.
When setting (moved dis-
tance and speed) which
cannot be omitted is omit-
ted or the set value of
another axis is input.
Confirm the pro-
gram form after of
each instruction.
Global error
3006
The label to the CALL and
the JUMP instruction is
absent.
Program the label at
the jump destina-
tion the call ahead.
3007
The CALL instruction is
defective.
Nest levels exceeds 15
piles. Or, the CALL does
not correspond to the
label of the RET.
Adjust nest levels to
15 piles or less.
Moreover, please
confirm the lavel
number.