81
CHAPTER 8 FUNCTIONS
8
8.10 Scaling Function
(3) Setting procedure
1. Set "A/D conversion enable/disable setting" to "0: Enable".
Project window [Intelligent Function Module] module name [Parameter]
2. Set "Scaling enable/disable setting" to "0: Enable".
3. Set values for "Scaling upper limit value" and "Scaling lower limit value".
Even if you set the scaling upper limit value and the scaling lower limit value in such a way that the change is larger than
the resolution, the resolution will not increase.
Your scaling settings must meet the following condition:
Scaling upper limit value > Scaling lower limit value
Item Setting range
Scaling upper limit value
-32000 to 32000
Scaling lower limit value