We recommend that you wait for 30 minutes before you continue with the further installation
steps. The thread adhesive only cures under pressure i.e. in the thread grooves of the pipe
connection. For this reason, any excessive thread adhesive should be removed using a clean
cloth.
Remark: The adhesive has completely cured and achieved resistance against environmental in-
fluences after one week.
Note!!!
The following steps must be carried out in accordance with company
procedures. Work carefully and prevent air getting into the transformer.
Use a container to collect any leaking oil.
Unscrew the vent screw by 3 or 4 turns anti-clockwise using the long size 4 hexagon key (vent-
ing is active).
Open the transformer gate valve very carefully until oil runs out of the sample hose. Allow the
escaping oil to run into a container.