EasyManua.ls Logo

MSA Chillgard 5000 - Communications Output

MSA Chillgard 5000
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
Initial Setup
Chillgard 5000
US
5.5 Communications Output
There are three options available to support digital outputs.
For a list of the registers that are available for exchange with the Modbus controller, refer to
Section 17, "Appendix D: Modbus Holding Registers".
For a list of the BACnet Objects that are available for exchange with the BACnet controller, refer to
Section 18, "Appendix E: BACnet Objects".
(8) The "Initial Setup" screen shows a check mark beside
the "Relay Configuration" step to indicate that it is
complete. Select "Continue" to go to the output config-
uration setup.
(1) On the "Digital" tab of the "Outputs" screen, select one
of the following:
(2) If "None" is selected, no digital communication is
configured.
(3) If "Modbus" is selected, do the following:
a) Select "Edit".
b) Select the "Device Address" field, and use the
alphanumeric keypad pop-up to enter a value.
Select to accept the value.
c) Select a baud rate for the connection.
d) Select the RS485 Termination check box.
e) Select "Done".

Table of Contents

Other manuals for MSA Chillgard 5000

Related product manuals