S12 ANALOG I/O 4. SETPOINT PROGRAMMING
4-70
Table 4-4 ANALOG OUTPUT PARAMETER SELECTION TABLE
ANALOG OUTPUT PARAMETER SELECTION TABLE
DEFAULT
PARAMETER NAME
RANGE / UNITS STEP
Minimum
Maximum
Phase A Current ............................. 0-100000 AMPS 1 0 100
Phase B Current ............................. 0-100000 AMPS 1 0 100
Phase C Current ............................. 0-100000 AMPS 1 0 100
Avg. Phase Current ........................ 0-100000 AMPS 1 0 100
AB Line Voltage............................... 50-20000 VOLTS 1 3200 4500
BC Line Voltage .............................. 50-20000 VOLTS 1 3200 4500
CA Line Voltage .............................. 50-20000 VOLTS 1 3200 4500
Avg. Line Voltage ........................... 50-20000 VOLTS 1 3200 4500
Phase AN Voltage .......................... 50-20000 VOLTS 1 1900 2500
Phase BN Voltage .......................... 50-20000 VOLTS 1 1900 2500
Phase CN Voltage .......................... 50-20000 VOLTS 1 1900 2500
Avg. Phase Voltage ........................ 50-20000 VOLTS 1 1900 2500
Hottest Stator RTD ......................... -50 to +250°C or -58 to +482°F 1 0 200
Hottest Bearing RTD ....................... -50 to +250°C or -58 to +482°F 1 0 200
Ambient RTD .................................. -50 to +250°C or -58 to +482°F1 -50 60
RTD #1 - 12 .................................... -50 to +250°C or -58 to +482°F 1 -50 250
Power Factor .................................. 0.01 to 1.00 lead/lag 0.01 0.8 lag 0.8lead
Reactive Power .............................. -50000 to 50000 kvar 1 0 750
Real Power ..................................... -50000 to 50000 kW 1 0 1000
Apparent Power .............................. 0 to 50000 kVA 1 0 1250
Thermal Capacity Used .................. 0-100 % 1 0 100
Relay Lockout Time ........................ 0-500 MINUTES 1 0 150
Current Demand ............................. 0-100000 AMPS 1 0 700
kvar Demand .................................. 0 -50000 kvar 1 0 1000
kW Demand .................................... 0 -50000 kW 1 0 1250
kVA Demand .................................. 0 -50000 kVA 1 0 1500
Motor Load ..................................... 0.00 - 20.00 x FLA 0.01 0.00 1.25
Analog Inputs 1-4 ........................... -50000 to +50000 1 0 +50000
Tachometer ..................................... 100 to 7200 RPM 1 3500 3700
MWhrs............................................. 0.000 to 999999.999 MWhrs 0.001 50.000 100.000
Analog In Diff 1-2............................. -50000 to +50000 1 0 100
Analog In Diff 3-4............................. -50000 to +50000 1 0 100
Torque............................................. 0 to 999999.9 0.1 0 100