EasyManua.ls Logo

Multilin SR469 - Function Code 07 - Read Device Status

Multilin SR469
270 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SUPPORTED MODBUS FUNCTIONS 6. COMMUNICATIONS
6-10
6.3.6
FUNCTION CODE 07 - READ DEVICE STATUS
Modbus Implementation: Read Exception Status
SR469 Implementation: Read Device Status
This is a function used to quickly read the status of a selected device. A short message length allows for rapid reading of status. The
status byte returned will have individual bits set to 1 or 0 depending on the status of the slave device.
SR469 General Status Byte:
LSBit B0: R1 Trip relay operated = 1
B1: R2 Auxiliary relay operated = 1
B2: R3 Auxiliary relay operated = 1
B3: R4 Alarm relay operated = 1
B4: R5 Block Start relay operated = 1
B5: R6 Service relay operated = 1
B6: Stopped = 1
MSBit B7: Running =1
Note:
if status is neither stopped or running, motor is starting.
Message Format and Example:
Request status from slave 11.
Master Transmission Bytes Example (hex)
SLAVE ADDRESS 1 0B message for slave 11
FUNCTION CODE 1 07 read device status
CRC 2 47 CRC calculated by the master
42
Slave Response
SLAVE ADDRESS 1 0B message for slave 11
FUNCTION CODE 1 07 read device status
DEVICE STATUS 1 59 status = 01011001 in binary
CRC 2 C2 CRC calculated by the slave
08

Table of Contents

Related product manuals