Crop Management Technologies
# Parameter Explanation Unit/Range Default
10.
Screen
Position when
external
contact occurs
If working with an external contact,
define the screen position percentage
when an event occurs
0 - 100% 0
11.
Use Fan & Pad
influence
Select whether the screen spreading
will be influenced by a Fan & Pad event
Yes/No No
12.
Screen
Position
during Fan &
Pad
Set the screen position percentage
when a Fan & Pad event occurs
0 - 100% 0
13.
Radiation
delay for
spreading
FOR SHADING SCREEN ONLY!
Define the time to wait before
spreading the screen once a radiation
condition is detected. The system will
check to see that the condition is still
true after the delay, before it begins to
spread the screen
mm:ss 00:00
14.
Radiation
delay for
collecting
FOR SHADING SCREEN ONLY!
Define the time to wait before
collecting the screen once a radiation
condition is detected. The system will
check to see that the condition is still
true after the delay, before it begins to
collect the screen
mm:ss 00:00
15.
Temp gap
curve
In cases where the screen is spread to
100%, and the measured
temperature/humidity is high, the
screen should be opened a little to
allow heat to escape from the
greenhouse.
Define the four point conversion table
that indicates the influence of the
temperature/humidity level on the
screen position.
0
o
to +50
o
C
0 - 100%
0
16.
Humidity gap
curve
0
o
to +50
o
C
0 - 100%
0