NMC-PRO
USER GUIDE
Doc. Name: NMC-PRO ׀ User Guide Ver 3.05.03 Revision: 2.2 Page: 67
Crop Management Technologies
STATUS FAN & PAD (MENU 4.5)
1. Fan & Pad active Displays if the Fan & Pad is currently operating
2. Fan & Pad start tempTemperature at which the Fan & Pad process begins
3. Number of active fans Displays how many fans are currently active
4. Pad Pump statusDisplays the current activity of the pad pump
5. Air inlet calculated position Displays the position the air inlet should be with all
influences considered
6. Air inlet measured position Displays the position the air inlet should be with all
influences considered
7. LimitationDisplays if there is a restriction on the Fan & Pad process due to a
higher priority event
8. Fan stage #Fan stage number according to Fan & Pad Program menu (1.5)
9. Start tempTemperature at which the fan stage starts operating
10. Stop temp Temperature at which the fan stage stops operating
11. StatusFan stage status
12. Limitation Displays if there is a restriction on the Fan Stage due to a higher priority
event
4.5 Fan_Pad Stat
Zone 1
19/01/09 16:21
1. Fan&Pad active
2. Fan&Pad start temp °C
3. Number of active fans
4. Pad Pump status
5. Air inlet calc. pos %
6. Air inlet meas. pos %
7.
Limitation
Temp
26.0
2
Off
0
0
None
Fan Stage Status
8. Fan stage #
9. Start temp °C
10. Stop temp °C
11. Status
12. Limitation
1
26.0
24.0
On
None
2
27.0
25.0
On
None
3
28.0
26.0
On
None