Doc. Name: NMC-PRO ׀ User Guide Ver 3.05.03 Revision: 2.2 Page: 53
Crop Management Technologies
2. Heating Network (Menu 7.3.2)
# Parameter Explanation Unit/Range Default
1.
Heating Control
Select the network from the drop down
list to define it’s setup within the zone.
Network 1-4
Floating Network
2.
Period
It is possible to divide the day up to 6
periods. You can decide if the period is
On/Off.
ON/OFF
3.
Active
Updated by the controller
(For indication only)
Yes/No
4.
Start time
Start Time of the period. In case of
overlapping periods, the next period
overrides the previous period.
hh:mm --:--
5.
Maximum
Water
Temperature
The maximum allowed water
temperature in the specified heating
network.
Even if the calculated temperature is
higher than the set maximum water
temperature, it will be restricted by this
parameter.
0° to +150° C 50
6.
Minimum Water
Temperature
The minimum allowed water
temperature in the specified heating
network.
Even if the calculated temperature is
lower than the set minimum water
temperature, it will be restricted by this
parameter.
0° to +150° C 0
7.3.2 Heating net Zone 1 19/01/09 16:21
2. Period
3. Active
4. Start time hh:mm
5. Max water temp °C
6. Min water temp °C
7. Hum influence
8. LS Pump always on
9. Diff LS P. On °C
10. Diff LS P. Off °C
11. Diff HS P. On °C
On
Yes
06:00
100.0
0.0
No
5.0
3.0
20.0
On
Yes
15:00
90.0
5.0
No
5.0
3.0
16.0
Off