Doc. Name: NMC-PRO ׀ User Guide Ver 3.05.03 Revision: 2.2 Page: 62
Crop Management Technologies
SETUP – MISTING (MENU 7.4)
# Parameter Explanation Unit/Range Default
Mist valve number
There are up to eight misting valves available
for setup; each valve is defined separately
1-8
1.
Max Pulse
The maximum and minimum time that the
misting valve may be opened.
h:mm:ss 00:00
2.
Min Pulse h:mm:ss 00:00
3.
Max Pause
The maximum and the minimum pause time,
between pulses.
h:mm:ss 00:00
4.
Min Pause h:mm:ss 00:00
5.
Calculated Spray
Values displayed are according to the set
point that starts the misting process and the
measured value inside the greenhouse. The
value varies between the minimum and the
maximum values of the ON/OFF time, which
are defined in the Misting Program.
h:mm:ss 00:00
6.
Calculated Pause h:mm:ss 00:00
7.
Calculated Cycle
Cycle duration, beginning from when the
valves are turned on and off, and until they
start running again.
Ex: If there is one misting valve, then the
calculated cycle time is the Spray time + the
pause time.
h:mm:ss 00:00
8.
Status
The current state of each valve.
Mist valve #
1. Max pulse
2. Min pulse
3. Max pause
4. Min pause
1
0:01:00
0:00:05
0:05:00
0:00:10
2
0:01:00
0:00:05
0:05:00
0:00:10
3
0:00:00
0:00:00
0:00:00
0:00:00
6. Calc. Spray
7. Calc. Pause
8. Calc. Cycle
9. Status
0:00:35
0:04:00
0:04:35
Spray
0:00:55
0:04:55
0:05:50
Wait
0:00:00
0:00:00
0:00:00
Off