Doc. Name: NMC-PRO ׀ User Guide Ver 3.05.03 Revision: 2.2 Page: 52
Crop Management Technologies
SETUP – HEATING (MENU 7.3)
1. Heating ON/OFF (Menu 7.3.1)
# Parameter Explanation Unit/Range Default
1.
Maximum temp
limit
Define the greenhouse temperature at
which the On/Off heating does not
operate
0 - 40° C 25
2.
Maximum CO2
concentration
Define the CO2 concentration at which the
On/Off heating does not operate.
Note: This parameter is enabled only if it
the On/Off heating system is the CO2
supplier which enriches the Greenhouse
with heating and CO2 (same value as in
the CO2 application setup).
0 - 5000 ppm 1500
3.
Heating On
delay
Define the time delay for the system to
verify that the heater ON trigger is true
before turning the heater ON
mm:ss 00:00
4.
Heating Off
delay
Define the time for the system to verify
that the heater OFF trigger is true before
turning the heater OFF
mm:ss 00:00
5.
Minimum On
time
Define the minimum time duration for the
heater to be ON
hh:mm 00:00
6.
Minimum Off
time
Define the minimum time duration for the
heater to be OFF
hh:mm 00:00
7.
Release for CO
2
Select YES to permit CO
2
to control the
ON/OFF Heating when the CO
2
is set to
Passive mode
Yes/No No
7.3.1 Heating On/ Zone 1 19/01/09 16:21
2. Max CO2 concentration ppm
3. Heating On delay mm:ss
4. Heating Off delay mm:ss
5. Minimum On time hh:mm
6. Minimum Off time hh:mm
7. Release for CO2
1500
05:00
05:00
01:00
00:20
No