80 Unidrive M Regen Design Guide
Issue Number: 4
Figure 5-5 Regen inductor type 3 dimensions
Location and mounting of the Regen inductor must be considered to ensure the following:
1. Natural cooling is present with no enclosures or guards fitted around the Regen inductor.
2. Natural cooling can travel through and over the Regen inductor as designed with the correct mounting.
3. For long cable applications forced cooling may be required, therefore additional space is required.
4. Regen chokes are suitably located to prevent damage to heat sensitive components.
5. Regen chokes are located away from flammable components to prevent fire risk.
Mounting of the Regen inductor in the base of the enclosure is possible as shown below. The mounting brackets as standard are located on the
bottom of the Regen inductor allowing the base mounting. Base mounting is the standard configuration and can be used with the complete range of
Regen inductors.
Figure 5-6 Standard Regen inductor base mounting
The Regen inductor can also be mounted on the back panel of the enclosure as shown following with the windings in a vertical orientation. If mounting
on the back panel is required the Regen inductor must be located as shown to ensure correct air flow across the Regen inductor and to maintain
correct mechanical support.
A2 B2 C2
A1 B1 C1
H
L
D
TH