9RLFH $ODUP 6
VWHPV
AMG-1 and AMG-E Audio Message Generator
58 AFC-600 Operations PN 51033:A 3/8/99
$0* DQG $0*( 7RQH0HVVD
H 6HOHFWLRQV $0* 6: 2II
Table 22 lists
the audio tone and message selections available when SW2 DIP 2 (Tone/Message
switch) is Off.
7DEOH 6HWWLQ
$0* 7RQHV DQG 0HVVD
HV $0* 6: 2II
Notes:
1. MPS-6 Notification Appliance Circuit 1 (NAC 1) can be manually selected with an
ACM-16AT to produce a desired tone or can be activated through
Control-By-Event by a Non-Alarm input.
2. If selecting a VROM or VRAM, and a VROM or VRAM chip is not installed, a
trouble indication appears at the AMG-1 when the message is due to begin and the
AMG-1 generates the interrupted 1 kHz default tone.
AMG-1 SW2 Rocker
Switches
System
Status
NAC 1 (B01)
Condition
Audio Tone or Message
S6 S7 S8
X X X No Alarm Off Standby
Off
Off
Off
Off
Off
Off
No Alarm
Alarm
On
X
1000 Hz 0.5 sec on, 0.5 sec off
Slow whoop
Off
Off
Off
Off
On
On
No Alarm
Alarm
On
X
Horn
120 ppm (March Time)
Off
Off
On
On
Off
Off
No Alarm
Alarm
On
X
Horn
Yel p
Off
Off
On
On
On
On
No Alarm
Alarm
On
X
Yel p
Wail
On
On
Off
Off
Off
Off
No Alarm
Alarm
On
X
3 slow whoops, VRAM-B message plays
3 slow whoops, VRAM-A message plays
On
On
Off
Off
On
On
No Alarm
Alarm
On
X
VROM-B message plays
VROM-A message plays
On
On
On
On
Off
Off
No Alarm
Alarm
On
X
20 ppm (Two-Stage)
VROM-A and VROM-B play
On
On
On
On
On
On
No Alarm
Alarm
On
X
Horn
NFPA Uniform Code 3
Temporal pattern fast whoop
X = Indicates that switch or control point can be On or Off.
Technical Manuals Online! - http://www.tech-man.com