EasyManuals Logo
Home>Omron>Temperature Controller>E5CSV

Omron E5CSV User Manual

Omron E5CSV
110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #101 background imageLoading...
Page #101 background image
Parameter Operation Lists
A-11
Appendices
Initial Setting Level (4)
Parameters
Mode
indicators
/displayed
text
Setting (monitor) value Default Unit
Set
value
Alarm 1 ON delay SP mode
0 to 999
0 Second
Alarm 1 OFF delay ALM mode
0 to 999
0 Second
0, 9: No alarm
1: Upper-/lower-limit
2: Upper limit
3: Lower limit
4: Upper-/lower-limit range
5: Upper- and lower-limit with standby sequence
6: Upper-limit with standby sequence
7: Lower-limit with standby sequence
Alarm 1 type IS mode
al
8: Absolute-value upper-limit
2 None
0: Closed in alarm Alarm 1 open in alarm IS mode
nc
1: Open in alarm
0 None
0: Latch OFF Alarm 1 latch IS mode
lt
1: Latch ON
0 None
Initial Setting Level (5)
Parameters
Mode
indicators
/displayed
text
Setting (monitor) value Default Unit
Set
value
Alarm 2 ON delay SP mode
0 to 999
0 Second
Alarm 2 OFF delay ALM mode
0 to 999
0 Second
0: No alarm
1: Upper-/lower-limit
2: Upper limit
3: Lower limit
4: Upper-/lower-limit range
5: Upper- and lower-limit with standby sequence
6: Upper-limit with standby sequence
7: Lower-limit with standby sequence
Alarm 2 type IS mode
al
8: Absolute-value upper-limit
2 None
0: Closed in alarm Alarm 2 open in alarm IS mode
nc
1: Open in alarm
0 None
0: Latch OFF Alarm 2 latch IS mode
lt
1: Latch ON
0 None

Table of Contents

Other manuals for Omron E5CSV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CSV and is the answer not in the manual?

Omron E5CSV Specifications

General IconGeneral
BrandOmron
ModelE5CSV
CategoryTemperature Controller
LanguageEnglish

Related product manuals