Parameter Operation Lists
A-11
Appendices
Initial Setting Level (4)
Parameters
Mode
indicators
/displayed
text
Setting (monitor) value Default Unit
Set
value
Alarm 1 ON delay SP mode
0 to 999
0 Second
Alarm 1 OFF delay ALM mode
0 to 999
0 Second
0, 9: No alarm
1: Upper-/lower-limit
2: Upper limit
3: Lower limit
4: Upper-/lower-limit range
5: Upper- and lower-limit with standby sequence
6: Upper-limit with standby sequence
7: Lower-limit with standby sequence
Alarm 1 type IS mode
al
8: Absolute-value upper-limit
2 None
0: Closed in alarm Alarm 1 open in alarm IS mode
nc
1: Open in alarm
0 None
0: Latch OFF Alarm 1 latch IS mode
lt
1: Latch ON
0 None
Initial Setting Level (5)
Parameters
Mode
indicators
/displayed
text
Setting (monitor) value Default Unit
Set
value
Alarm 2 ON delay SP mode
0 to 999
0 Second
Alarm 2 OFF delay ALM mode
0 to 999
0 Second
0: No alarm
1: Upper-/lower-limit
2: Upper limit
3: Lower limit
4: Upper-/lower-limit range
5: Upper- and lower-limit with standby sequence
6: Upper-limit with standby sequence
7: Lower-limit with standby sequence
Alarm 2 type IS mode
al
8: Absolute-value upper-limit
2 None
0: Closed in alarm Alarm 2 open in alarm IS mode
nc
1: Open in alarm
0 None
0: Latch OFF Alarm 2 latch IS mode
lt
1: Latch ON
0 None