Section 5 Parameters
5-26
Parameters
IS mode (1)
Alarm 2 type
al
Select one of the following nine alarm 2 types:
Set
value
Alarm type
Alarm output
operation
0 Alarm function OFF Output OFF
1 Upper- and lower-limit
2 Upper-limit
3 Lower-limit
4 Upper- and lower-limit range
5
Upper- and lower-limit with
standby sequence
6
Upper-limit with standby
sequence
7
Lower-limit with standby
sequence
8 Absolute-value upper-limit
* Alarm values 1 to 7: Set the deviation from the SP (set point) in the
alarm value (X).
Alarm 8: Set the absolute value from 0°C/°F in the alarm value (Y).
* The default is 2 (upper-limit alarm).
* This parameter is displayed regardless of the output assignment
setting.
OFF
ON
SP
XX
ON
OFF
SP
XX
OFF
ON
SP
XX
OFF
ON
SP
X
OFF
ON
SP
X
OFF
ON
SP
X
OFF
ON
SP
X
OFF
ON
Y
Function
Setting