F3SG-SR/PG
70
Manual Reset Mode with Intelligent Tap
[Wiring Example]
Note: 1. When using the Intelligent Tap (F39-SGIT-IL3) with the emitter and receiver connected, the following functions are not available.
• External Test
• Operating Range Selection by wiring
• Optical Synchronization
2. For the functional earth connection, refer to page 66.
S1
F39-SGIT-IL3
24 VDC
IO-Link
Master
*5
Wiring for NPN *1
*6
24 VDC
F39-JGB-L/
XS5F-D521-DJ0-IL
F39-JG
A-D
F39-JGR3K-L and
F39-JGB-L
F39-JGR3K-D and F39-JGB-D
IN
PLC
*2
IN1
IN2
S1: Lockout/interlock reset switch
PLC: Programmable logic controller (Used for monitoring only.
NOT related to safety system.)
Timing chart
Beam state: Unblocked
Blocked
Reset switch (S)
OSSD
Receiver
Emitter
OSSD 1 (Black)
OSSD 2 (White)
24V/0V (Brown)
0V/24V (Blue)
AUX (Red)
MUTE B (Pink)
MUTE A (Gray)
RESET/EDM
(Yellow)
Safety controller
*3 *4
IntelligentTap
Needed
*1. Reverse the polarity of the power supply when using in the NPN
system. Select a PLC and a safety controller of PNP or NPN type
according to the system of your application.
*2. When connecting to the PLC, the output mode must be changed with
the SD Manager 3 according to your application. For the setting this
function, refer to the User's Manual (Man.No.Z405).
*3. Refer to page 75 for more information.
*4. The safety controller and the F3SG-SR must share the power supply
or be connected to the common terminal of the power supply.
*5. For connecting with the IO-Link Master unit, refer to an instruction
manual of the IO-Link Master unit you use.
*6. This is the case for a PELV circuit.
: Indicates a switch position.
Function
Setting
DIP switch SD Manager 3
EDM EDM Disabled [External device monitoring] : Disable
Interlock
Manual Reset (Start/
Restart Interlock)
[Start interlock] : Enable
[Restart interlock] : Enable
Operating Range Selection Long [Operating Range Selection] : Long mode
Non-Muting system
Perform wiring according to the wiring diagram.
N/A [Muting] : Disable
Test Input N/A
Wired Synchronization Connect the emitter and receiver with the Intelligent Tap.
3ON
4ON
5ON
8ON