Functions and Operations
5.13 Averaging Inputs
5-39
The data refresh periods when averaging is used are given by
model in the following table.
Averaging is set using the following parameters.
* To not use averaging, set the average type “avg-t” to smpl and the
averaging times “avg-n” to 1.
Parameter Setting Procedure
Set value K3HB-X/V/H K3HB-S
No
averaging
1 20 ms 0.5 ms
Simple
average
2 40 ms 1 ms
4 80 ms 2 ms
8 160 ms 4 ms
16 320 ms 8 ms
32 640 ms 16 ms
64 1.28 s 32 ms
128 2.56 s 64 ms
256 5.12 s 128 ms
512 10.24 s 256 ms
1024 20.48 s 512 ms
Moving
average
1 to 1024
20 ms 0.5 ms
Parameter Set value Meaning of set value
Average type
avg-t
smpl Simple average
move Moving average
Averaging times
avg-n
1 1
2 2
4 4
8 8
16 16
32 32
64 64
128 128
256 256
512 512
1024 1024
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
L
0
” is displayed on the level/bank
display to indicate the initial setting level.
avg-t
L 1
(AVG-T)
avg-n
L 1
(AVG-N)
L
Displays “L 0.”
L 0