Functions and Operations
5.14 Detecting Sudden Input Changes
5-43
Compensating forced-zero references → P.5-70
Delaying output OFF timing
→ P.5-52
Holding already output comparative outputs
→ P.5-55
D
Use the
U
[UP] and
S
[SHIFT] Keys to set the
password “
-0169
.” Press the
M
[MODE] Key
to move to the advanced function setting level.
•
“
L
f
” is displayed on the level/bank display to
indicate the advanced function setting level.
E Press the M [MODE] Key to change
the PV display to “hp-f.”
F Press the S [SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
G Use the U [UP] Key to change the set
value.
H Press the M [MODE] Key to switch to
the next parameter.
• The set value is registered.
I Press the L [LEVEL] Key for at least
1 s to return to the initial setting level.
1 s min.
J Press the L [LEVEL] Key for at least
1 s to return to RUN level.
1 s min.
SU
M
init
Displays “L f.”
off
L f
M
hp-f
off
L f
S
hp-f
off
L f
U
hp-f
on
L f
M
bnk-c
off
L f
L
L 0
L
123. 4
123. 4
Remarks
Number of measurements
Input value Display value Comparative value for the next input
1 4.0 4.0-4.0=0 4.0
2 3.0 3.0-4.0=-1.0 (4.0+3.0)=3.5
3 4.5 4.5-3.5=1.0 (3.5+4.5)=4.0
4 3.0 3.0-4.0=-1.0 (4.0+3.0)=3.5
5 8.5 8.5-3.5=5.0 (3.5+8.5)=6.0
Input waveform
0 [V]
ON
OFF
Timing input
Example of Previous Average Value Comparison for Sampling Hold
1
2
1
2
1
2
1
2