ation
Section 6 User Calibration
6-8
K3HB-H (TC Input)
Perform step F and then perform bias compensation.
I Use the U [UP] Key to change the set
value to “yes.”
J Press the M [MODE] Key.
• The calibration value is “registered.”
• When there are two inputs, input B is
calibrated next. Connect the
reference device to input B and
repeat steps D to J (K3HB-S only).
K Turn ON the power again and check
the operation.
L Press the M [MODE] Key to change to
bias calibration.
• Disconnect the standard voltage
generator or standard current
generator.
• Turn ON the thermocouple of the cold
junction compensator. Make sure the
cables for the standard voltage
generator or standard current
generator are disconnected at this
time.
• Calibration values are not displayed
when bias compensation values are
being monitored. (The value that is
read is not a bias value. Instead, the
display shows calibration values for
the main inputs.)
U
yes
L u
str
M
bias
L u
Leave open.
Output Input
Zeroing
controller
DMM
STV
Short
Zeroing
controller
DMM
STV
Disconnect to open.
This is the compensating
conductor for the selected
thermocouple. However the
compensating conductor for
thermocouple K is used for
thermocouples E, R, S, B, and W.
This is the compensating
conductor for the selected
thermocouple. However the
compensating conductor for
thermocouple K is used for
thermocouples E, R, S, B, and W.
Output Input