Section 3 Basic Application Methods
3-12
RUN Level
✽ Check on the status displays.
Initial Setting Level (L 0) The Setting Level Protect setting must be set to 0 (SET.PT=0) to
enable moving to the advanced function setting level.
Advanced Function Setting
Level (
L f)
ON
OFF
1000.0°C
200.0°C
500.0°C
800.0°C
Comparative set value HH
Comparative set value H
Comparative set value L
Comparative set value LL
Output HH
Output H
Output PASS
Output L
Output LL
Zone Outputs
Display
High
Low
Parameter
Characters
Set
value
Remarks
Comparative
set value HH
✽
1000.
0
Control example for the following
settings:
Upper limit warning: 1,000.0
°C
Heating output: 800.0
°C
Cooling output: 500.0
°C
Lower limit warning: 200.0
°C
Comparative
set value H
✽
800.
0
Comparative
set value L
✽
500.
0
Comparative
set value LL
✽
200.
0
Parameter
Characters
Set value Remarks
Input type A in-ta 11-r Set the R thermocouple
sensor range.
Temperature
unit
d-u c Set the temperature unit
to
°C.
Comparative
output pattern
out-p zone Zone outputs
Move to
advanced
function
setting level
amov -0169 Move to advanced func-
tion setting level to set the
standby sequence.
Parameter
Characters
Set value Remarks
Standby
sequence
stdby on Enable the standby
sequence.