User Calibr
ation
Section 6 User calibration
6-6
● Input type and parameter/reference signal
G Repeat steps D to F to temporarily
register the calibration lower limit.
• When temporary registration has
been completed, the parameter for
registration "str" is displayed.
H Press the S[SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
I Use the U[UP] Key to change the set
value to "yes".
J Press the M[MODE] Key.
• The calibration value is "registered".
• When there are two inputs, input B is
calibrated next. Connect the
reference device to input B and
repeat steps D to J.
K Turn ON the power again and check
the operation.
Input
Input
type
Calibration upper limit Calibration lower limit
Parameters
Reference
signal
Parameters
Reference
signal
A
0 to 20
m
A,
4 to 20
m
A
aaa20 20.00
m
A aaa 4 4.00
m
A
0 to 5 V,
1 to 5 V
aaa 5 5.000 V aaa 1 1.000 V
±5 V aaa 5 5.000 V aaa-5 -5.000 V
±10 V aaa10 10.000 V aaa-10 -10.000 V
B
0 to 20
m
A,
4 to 20
m
A
baa20 20.00
m
A baa 4 4.00
m
A
0 to 5 V,
1 to 5 V
baa 5 5.000 V baa 1 1.000 V
±5 V baa 5 5.000 V baa-5 -5.000 V
±10 V baa10 10.000 V baa-10 -10.000 V
str
no
L
u
S
str
no
L
u
U
yes
L
u
str