Functions and Operations
5.21 Setting the present measurement value to "0" again using the forced-zero reference
5-55
Tare zero is set using the following parameter.
Parameter Setting Procedure
Parameter Set value Meaning of set value
Tare zero
t-zr
on Tare zero enabled
off Tare zero disabled
A Press the L[LEVEL] Key for at least 3
s in RUN level to move to the initial
setting level.
3 s min.
•"
L
0" is displayed on the level/bank
display to indicate the initial setting
level.
B Press the M[MODE] Key several times
to change the PV display to "amov".
• This parameter is not displayed for
the initial status due to setting level
protect.
Refer to "Limiting Key Operations"
(P.5-80) for information on removing
setting level protect.
C Press the S[SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
D Use the U[UP] and S[SHIFT] Keys to
set the password "-0169". Press the
M[MODE] Key to move to the
advanced-function setting level.
•"
L
f" is displayed on the level/bank
display to indicate the advanced-
function setting level.
E Press the M[MODE] Key several times
to switch the PV display to "t-zr".
F Press the S[SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
G Use the U[UP] Key to change the set
value to "on".
• Change the set value to "off" to turn
OFF tare zero.
t-zr
L
f
(T-ZR)
L
cal
0
Displays "
L
0".
L
0
M
amov
0
L
0
S
amov
00000
L
0
SU
M
init
Displays "
L
f".
off
L
f
M
t-zr
off
L
f
S
t-zr
off
L
f
U
t-zr
on
L
f