EasyManuals Logo

Omron M1 Series User Manual

Omron M1 Series
808 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #102 background imageLoading...
Page #102 background image
Wiring for Main Power Supply Input Terminals (L1/R, L2/S, L3/T)
The following describes the wiring for the main power supply input terminals and for peripheral equip-
ment.
Installing molded case circuit breaker
If the inverter’s protective function is activated, the inverter internal circuit may be damaged de-
pending on the condition.
Be sure to connect the main power supply input terminals (L1/R, L2/S, L3/T) to the power supply
via a molded case circuit breaker (MCCB) according to each inverter.
When using multiple inverters, install one MCCB per inverter
.
Determine the capacity of the MCCB according to the molded case circuit breaker (MCCB) value
shown in the previous table.
Determine the time characteristic of the MCCB upon due consideration of the time characteristic
of the inverter’s overheat protection function (150% of the rated output current for one minute).
If you must share one MCCB with multiple inverters or other equipment, construct a sequence
that turns OFF the power supply via the alarm output signal, as shown in the figure below.
L1/R
L2/S
L3/T
ROB
ROC
X
X
X
ONOFF
MC
MCCB
Three-phase 200 VAC
Three-phase 400 VAC
Power
supply
Inverter
Alarm signal
*2
(NC contact)
*1
*1. For 400-V class, connect a 400/200-V transformer.
*2. Set the Output Terminal [ROA, ROB] Function Selection (E27) to “1099: AL (Alarm signal).”
Installing earth leakage breaker
When selecting the earth leakage breaker to use between the power supply and the main power
supply input terminals (L1/R, L2/S, L3/T), consider the following.
High-frequency leakage current from inverter
The inverter produces a high-frequency leakage current due to its high-speed output switching.
In general, a leakage current of approx. 100 mA will flow for the power cable length of 1 m per in-
verter
. Moreover
, an additional leakage current of approx. 5 mA will flow with the increasing length
by 1 m.
Therefore, an earth leakage breaker to use in the power input section must be dedicated for the
inverter
, which removes high-frequency leakage current and detects only the leakage current in a
frequency range that is dangerous to the human body.
Select a special earth leakage breaker for the inverter with a sensitivity current rating of 10 mA or
higher per inverter.
2 Design
2-42
M1 Series Standard Type User's Manual (I669)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron M1 Series and is the answer not in the manual?

Omron M1 Series Specifications

General IconGeneral
Input Voltage200-240V AC
Output Voltage3-phase 200 to 240 VAC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus RTU
EnclosureIP20
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m
Frequency Range0.5-400 Hz
Storage Temperature-20°C to +65°C

Related product manuals