EasyManua.ls Logo

Omron M1 Series - Page 773

Omron M1 Series
808 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Symptom Possible cause Remedy
Refer-
ence
page
The motor or
machine caus-
es a loud noise.
The carrier frequency is too low. Increase the Carrier Frequency (F26). Howev-
er, this may increase noise or leakage current
from the inverter. In addition, the output cur-
rent must be derated depending on the model.
For details, refer to
A-1 Derating Table on
page A-2.
page
7-113
page
A-2
The frequency of the motor in ro-
tation resonates with the ma-
chine's natural frequency.
Change the frequency setting. If resonance
occurs during acceleration/deceleration, use
the Jump Frequency (C01 to C04) to avoid the
resonance frequency.
page
7-116
The motor is overexcited. Set the 1st Base Frequency (F04)/2nd Base
Frequency (A02), 1st Rated Voltage at Maxi-
mum Output Frequency (F06)/2nd Rated Volt-
age at Maximum Output Frequency (A04) ac-
cording to the motor ratings. If this does not
improve the condition, slightly lower the 1st
Rated V
oltage at Base Frequency (F05)/2nd
Rated Voltage at Base Frequency (A03) value.
Or set the 1st Drive Control Selection
(F42)/2nd Drive Control Selection (A14) to “0:
V/f control (No slip compensation),” or, if using
“V/f control with speed sensor,” use Non-linear
V/f Frequency 1 (E166)/Non-linear V/f Voltage
7 (E179) and perform tuning.
page
5-10
page
5-19
The inverter
trips with an
overcurrent pro-
tection (OLU).
The thermistor trip is not set ap-
propriately.
Disable Thermistor Function Selection (MOH)
(H26). Alternatively, adjust 1st Thermistor Er-
ror Detection Level (MOH) (H27).
page
7-88
The inverter
trips with an
overvoltage
protection
(OUn) during
deceleration.
The set deceleration time is too
short.
Increase the value set in the deceleration time
(F08/E11/E13/E15).
page
5-39
page
5-43
Anti-regenerative Control Function
Selection (H69) is set to “0: Disa-
ble.”
Enable Anti-regenerative Control Function Se-
lection (H69). However, when this function is
enabled, the actual deceleration time may be
longer than the set value. For details, refer to
7-8-2 Anti-regenerative Control Function on
page 7-85.
page
7-
85
If an overvoltage trip occurs during deceleration although Anti-regenerative Control
Function Selection (H69) is enabled:
The Frequency Rising Limit for
Torque Limit (H76) value is inap-
propriate.
Change the set values. For details, refer to
7-8-2 Anti-regenerative Control Function on
page 7-85.
page
7-85
The inverter
trips with a ther-
mistor error
(OH4).
24-VDC voltage is input to the
PTC terminal.
Remove 24-VDC voltage from the PTC termi-
nal. page
7-88
9 Troubleshooting
9-33
M1 Series Standard Type User's Manual (I669)
9-2 Troubleshooting
9

Table of Contents

Related product manuals