28
Chapter2
OS32C
User’s Manual
Operating States & Output Modes
Fig. 2-11 Object detection in Zone set B.
From the diagram, there is a period of time, Textend. Between tmin and tEndZoneA, where the system may
have switched to Zone set B already but it needs to protect Zone set A. This is covered in the following
section.
How to Guarantee Protection of Original Zone Set
Additional measures may be necessary to ensure that Zone set A maintains adequate monitoring up to
t
EndZoneA.
With t
start established relative to tDangerZoneB, we must compare tEndZoneA and tmin.
Case 1.
Zone set switching after the monitoring of zone set A is no longer required
(tEndZoneA tmin)
When t
EndZoneA tmin, no further modifications are necessary. Zone set A will be properly monitored for
the duration that is needed.
Case 2. Zone set may be switched before the monitoring of zone set A is no longer required
(tEndZoneA > tmin)
When t
EndZoneA > tmin, measures must be taken to ensure that Zone set A is protected even when the
monitoring zone is switched to zone set B before t
EndZoneA. A simple measure is to modify safety
distance (S) used when defining Zone set A such that it includes an additional component (Z
extra)
defined by the maximum approach speed (K) and a worst case extension time (T
extend) to account for
the time that Zone set A may not be monitored.
Z
extra = K * Textend = K * (tEndZoneA - tmin)
Expanding monitoring zone using this additional parameter Z
extra enables the OS32C to detect an
object in advance that may enter the actual monitoring zone of zone set A during zone set switching. In
other words, expanding the monitoring zone means that the timing of t
EndZoneA is shifted to tmin.
t
start
Start
switching
t
min
=
t
start
+ T
delay
-T
tol
Object detected
(earliest)
t
maxToOff
=
t
start
+ T
delay
+ T
tol
+
T
response
+ T
sample
Object detected
(latest)
T
delay
Zone set BZone set A
T
sample
Zone set A
OR
Zone set B
time
T
tol
T
delay
T
tol
T
response
t
DangerZoneB
t
EndZoneA
T
extend
T
maxReaction

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron OS32C Series and is the answer not in the manual?

Omron OS32C Series Specifications

General IconGeneral
Response Time80 ms
TypeSafety Laser Scanner
Protection StructureIP65
Safety CategoryType 3
Power Supply24 VDC
InterfaceEthernet/IP, PROFINET
Operating Temperature-10°C to 50°C
OutputOSSD
CommunicationEthernet/IP
ConfigurationVia software
Warning ZoneConfigurable

Related product manuals