41
Wiring Precautions Section 2-5
an insulating transformer and a line filter in the power supply section to
remove such noise.
Use twisted-pair cables for power supply lines. Use adequate grounds
(i.e., to 100 or less) with wire cross sections of 1.25 mm
2
or greater.
Use twisted-pair shielded cables for control voltage output signals, input
signals and encoder signals.
The maximum distance for the encoder signal from an encoder to the MC
Unit must not exceed 20 m.
The input terminals that operate the 24 V system are isolated with optical
couplers to reduce external noise effects on the control system.