15 Troubleshooting
15-30
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Event name SNMP Setting Error Event code 34260000 hex
Meaning An error was detected in the SNMP agent/trap settings.
Source EtherNet/IP Function Module Source details SNMP Detection
timing
At power ON or
Controller reset
Error attributes Level Minor fault Recovery Automatic recov-
ery (after down-
loading the
SNMP settings),
cycle the power
supply, or reset
Controller
Log category System
Effects User program Continues. Operation SNMP operation stops.
Indicators EtherNet/IP NET RUN EtherNet/IP NET ERR EtherNet/IP LINK/ACT
--- Flashes at 1-s intervals. ---
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
Setting error Identify the error from the attached
information, correct the setting, and
then download the settings again.
None
Power was interrupted when a down-
load was in progress for the SNMP
agent/trap settings.
Perform the Clear All Memory opera-
tion or download the settings again.
Do not turn OFF the power supply to
the Controller while a download is in
progress for the SNMP agent/trap
settings.
Memory error If operation is not recovered by the
above, replace the CPU Unit.
None
Attached
information
Attached information 1: Type of errors (01 hex: Non-volatile memory access error, 02 hex: Inconsistency in settings)
Attached information 2: Error location, when there is an inconsistency in the settings (01 hex: SNMP agent settings,
02 hex: SNMP trap settings)
Precautions/
Remarks
The cause of error can be identified with the attached information.