15-63
15 Troubleshooting
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
15-3 Checking Status with the Network Configurator
15
15-3-2 Connection Status Codes and Troubleshooting
OMRON error code
01 0810 Error code returned from target:
New data could not be obtained from
the CPU Unit when opening connec-
tion. (The Unit will automatically
recover, and attempt to open the
connection again.)
This error may occur
if the CPU Unit’s task
period was long
when opening the
connection or some
problem in the Con-
troller caused the
Controller to stop. If
the task period was
too long, operation
recovers automati-
cally. If the Controller
has stopped, iden-
tify the error from the
error information in
the CPU Unit.
The meaning of this
error code is defined by
each vendor, so it
depends on the target’s
specifications. (Con-
tact the target device’s
manufacturer.)
The meaning of this
error code is defined by
each vendor, so it
depends on the origina-
tor’s specifications.
(Contact the originator
device’s manufacturer.)
01 0811 Error code generated by originator:
New data could not be obtained from
the CPU Unit when opening connec-
tion. (The Unit will automatically
recover, and attempt to open the
connection again.)
This error may occur
if the CPU Unit’s task
period was long
when opening the
connection. If the
task period was too
long, operation
recovers automati-
cally.
The meaning of this
error code is defined by
each vendor, so it
depends on the target’s
specifications. (Con-
tact the target device’s
manufacturer.)
The meaning of this
error code is defined by
each vendor, so it
depends on the origina-
tor’s specifications.
(Contact the originator
device’s manufacturer.)
Connection status
Source of error
Handling
General
Status
(hex)
Additional
Status
(hex)
Configuration 1 Configuration 2 Configuration 3