5-39
5
Digital Reference Card: F3
Analog Output Option Card Setup: F4
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display V/f
V/f
with
PG
Open
Loop
Vector
1
Closed
Loop
Vector
F3-01
Digital input
option
Sets the Digital Reference
Card input method.
0: BCD 1% unit
1: BCD 0.1% unit
2: BCD 0.01% unit
3: BCD 1 Hz unit
4: BCD 0.1 Hz unit
5: BCD 0.01 Hz unit
6: BCD special setting (5-
digit input)
7: Binary input
6 is effective only, when the
DI-16H2 is used.
When o1-03 is set to 2 or
higher, the input will be BCD,
and the units will change to the
o1-03 setting.
0 to 70 NoAAAA390H6-149
DI Input
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEM
OBUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
F4-01
Channel 1
Monitor
Selection
This function is enabled when
the analog monitor card is
used.
Monitor selection: Sets the
number of the monitor item to
be output. (Numerical portion
 of U1-)
4, 10, 11, 12, 13, 14, 25, 28,
35, 39 and 40 cannot be set.
Gain: Sets the percentage of
the monitor item, which is
equal to 10V output.
Bias: Sets the percentage of
the monitor item, which is
equal to 0V output.
1 to 38 2 No A A A A 391H -
F4-02
Channel 1
Gain
0.0 to
100.0
100.0% Yes A A A A 392H -
F4-03
Channel 2
Monitor
Selection
1 to 38 3 No A A A A 393H -
F4-04
Channel 2
Gain
0.0 to
100.0
50.0% Yes A A A A 394H -
F4-05
CH1 Output
Bias
–110.0
to
110.0
0.0% Yes A A A A 395H -
F4-06
CH2 Output
Bias
–110.0
to
110.0
0.0% Yes A A A A 396H -
F4-07
Analog Out-
put Signal
Level CH1
Selects the analog output sig-
nal level for channel 1 (effec-
tive for the AO-12 option card
only).
0:0 to 10V
1:-10 to +10
Using an AO-08 option card
the possible outputs signal is 0
to +10V only. The setting of
F4-07 and F4-08 has no
effect.
0, 1 0 No A A A A 397H -
F4-08
Analog Out-
put Signal
Level CH2
0, 1 0 No A A A A 398H -