EasyManuals Logo

Omron VARISPEED F7 User Manual

Omron VARISPEED F7
389 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #147 background imageLoading...
Page #147 background image
5-46
5
D Braking resistor fault (ON: Resistor overheat or braking transistor fault) Yes Yes Yes Yes 6-63
E
Fault (ON: Digital Operator communications fault or fault other than CPF00 and
CPF01 has occurred.)
Yes Ye s Ye s Ye s 6-78
F Not used. (Set when the terminal is not used.) Yes Yes Yes Yes -
10 Alarm (ON: Alarm displayed) Yes Yes Yes Yes 6-78
11 Fault reset command active Yes Yes Yes Yes 6-78
12 Timer function output Yes Yes Yes Yes 6-98
13
f
ref
= f
out
agree 2 (detection width L4-04 is used)
Yes Ye s Ye s Ye s 6-33
14
f
out
= f
set
agree 2 (ON: Output frequency = L4-03, with detection width L4-04 is
used, and during frequency agree)
Yes Ye s Ye s Ye s 6-33
15
Frequency detection 3 (ON: Output frequency ≤ -L4-03, detection width L4-04 is
used)
Yes Ye s Ye s Ye s 6-33
16
Frequency detection 4 (ON: Output frequency ≥ -L4-03, detection width L4-04 is
used)
Yes Ye s Ye s Ye s 6-33
17 Overtorque/undertorque detection 1 NC (NC Contact, OFF: Torque detection) Yes Yes Yes Yes 6-49
18 Overtorque/undertorque detection 2 NO (NO Contact, ON: Torque detection) Yes Yes Yes Yes 6-49
19 Overtorque/undertorque detection 2 NC (NC Contact, OFF: Torque detection) Yes Yes Yes Yes 6-49
1A During reverse run (ON: During reverse run) Yes Yes Yes Yes 6-78
1B During baseblock 2 (OFF: During baseblock) Yes Yes Yes Yes 6-78
1C Motor selection (ON: Motor 2 selected) Yes Yes Yes Yes 6-79
1D During regenerative operation No No No Yes 6-79
1E Restart enabled (ON: Restart enabled) Yes Yes Yes Yes 6-61
1F
During motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the
detection level)
Yes Ye s Ye s Ye s 6-52
20 Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting) Yes Yes Yes Yes 6-64
30 During torque limit (current limit) (ON: During torque limit) No No Yes Yes 6-121
31 During speed limit No No No Yes 6-121
32
Activated if the speed control circuit (ASR) is operating for torque control. The
ASR output becomes the torque reference. The motor is rotating at the speed limit.
No No No Yes 6-121
33 Zero-servo end (ON: Zero-Servo completed) No No No Yes 6-129
36
Frequency (FOUT) detection 5 (like Frequency Detection 2, but OFF during base-
block; ON: Output Frequency ≥ +L4-01 or Output Frequency < -L4-01, L4-02 is
used)
Yes Ye s Ye s Ye s 6-33
37
During run 2 (ON: Frequency output, OFF: Baseblock, DC injection braking, initial
excitation, operation stop)
Yes Ye s Ye s Ye s 6-77
38 Drive enabled Yes Yes Yes Yes 6-79
3D Inverter’s Cooling Fan Fault detected Yes Yes Yes Yes 6-62
Setting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
loop
Vector
Closed
Loop
Vector

Table of Contents

Other manuals for Omron VARISPEED F7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron VARISPEED F7 and is the answer not in the manual?

Omron VARISPEED F7 Specifications

General IconGeneral
BrandOmron
ModelVARISPEED F7
CategoryInverter
LanguageEnglish

Related product manuals