Display and settings for the communication adaptor board
Various procedures
(04–01) Pulse count 1
(04–02) Pulse count 2
(04–03) Pulse count 3
•
Displays the current pulse count (P1, P2, P3).
•
If the pulse count value is changed, the distribution function of the Intelligent Controller will not operate properly.
[How to change]
1
Press and hold the SET key for at least 1 second and the pulse count value blinks.
2
Press the UP or DOWN key to change it to the pulse count value you want to set.
(Changeable range: 0 to 65535)
3
Press and hold the SET key and when the display changes from blinking to lit, the change is
completed.
(04–04) Interval for regular communication 2 of air conditioner linked system 1
(04–05) Interval for regular communication 2 of air conditioner linked system 2
•
Displays the interval for the air conditioner regular communication 2.
•
At factory shipment, the interval for regular communication 2 is 18 minutes.
[How to change]
1
Press and hold the SET key for at least 1 second and the regular communication interval (minutes)
will blink.
2
Press the UP or DOWN key to change it to the regular communication interval you want to set.
(Changeable range: 0 to 99)
3
Press and hold the SET key. When the display changes from blinking to lit, the change is completed.
•
Air conditioner regular communication 2 is not performed when 0 minutes is set.