26
Display and settings for the communication adaptor board
Various procedures
(04–12) Outdoor unit maintenance data not required
•
Use to reduce communication load by not acquiring outdoor unit data.
•
At factory shipment, it is set to acquire outdoor unit data.
[How to change]
1
Press and hold the SET key for at least 1 second and the rightmost digit '0' flashes.
2
Press the UP or DOWN key and '0' and '1' are alternately displayed.
0 Acquire outdoor unit maintenance data.
1 Do not acquire outdoor unit maintenance data.
3
Press and hold the SET key. When the display changes from blinking to lit, the change is completed.
(04–13) Central address settings
•
Use this when forcibly setting a central address to an indoor unit for which a central address is not set.
[Central address setting method]
1
Press and hold the SET key for at least 1 second.
2
If END is displayed on the 7-segment numerical display, the setting is completed.
(It is automatically set in order of indoor unit address in the range of 1 to 64)
* The central address of already set units is not changed.
Set unused central addresses in the order of address of unconfigured units.