23
Display and settings for the communication adaptor board
Various procedures
(04–06) Communication speed
•
Displays the communication speed of the communication adaptor control wiring.
•
The factory setting is 19,200 BPS.
 
•
The following BPS can be selected.
1
19200 BPS ... Intelligent Controller (Do not change from this setting)
2
9600 BPS ... AMY software
[How to change]
1
Press and hold the SET key for at least 1 second and the BPS value blinks.
2
Press the UP or DOWN key to display 19200 and 9600 alternately.
3
Press and hold the SET key. When the display changes from blinking to lit, the change is completed.
4
It becomes valid after power supply restart of the communication adaptor board.
(04–07) Communication error detection interval
•
Displays the time (minutes) until judging that a communication error with the air conditioner has occurred.
•
The factory setting is 10 minutes.
•
It can be set in the range from 0 to 99 minutes.
•
If it is set to 0 minutes, communication error detection will not be performed.