Creating Programs
4-34
4.4.6 Switching of Output Range (14-bit Mode Only)
When selecting the 14-bit mode in the analog I/O unit (FP0R-A21/A42), the output range can
be switched by user programs. It can be set for each channel.
I/O allocation (External output WY)
Y
3
F
Y
3
E
Y
3
D
Y
3
C
Y
3
B
Y
3
A
Y
3
9
Y
3
8
Y
3
7
Y
3
6
Y
3
5
Y
3
4
Y
3
3
Y
3
2
Y
3
1
Y
3
0
Y
2
F
Y
2
E
Y
2
D
Y
2
C
Y
2
B
Y
2
A
Y
2
9
Y
2
8
Y
2
7
Y
2
6
Y
2
5
Y
2
4
Y
2
3
Y
2
2
Y
2
1
Y
2
0
A
1
A
0
Output data of CH1 (14bit)
Input average setting: CH0
-CH3
CH1 output range setting
A
1
A
0
Output data of CH0 (14bit)
Input average setting: CH0
-CH3
CH0 output range setting
A1 A0 Item A1 A0 Item
0 0
CH1 output data setting 0 0 CH0 output data setting
0 1 Input a average setting 0 1 Input range setting
1 0
CH1 output range setting
1 0 CH0 output range setting
1 1 CH1 output data setting 1 1 CH0 output data setting
Each output range is specified by setting the following constants.
Item Description
Output range setting
Input constants for specifying output ranges in the 14-bit area.
H30 10 to +10V / 0 to 20mA
H31 5 to +5V / 4 to 20mA
H32 0 to 10V
H33 0 to 5V
Default settings
The default settings are as follows; Output range for all channels: Voltage output range: -10 to
+10 V, Current output range: 0 to 20 mA.
KEY POINTS