Parameter Reference 15-13
AC10 Inverter
Function
Code
Function
Definition
Setting Range
Mfr’s Value
Change
F627
Current Limiting when Flycatching
50-200
100
F631
VDC Adjustment Selection
0: Disabled
1: Enabled
0
F632
Target voltage of VDC adjustor (V)
200-800
Subject to
inverter
model
√〇
F633-
F637
Reserved
F638
Parameters copy enabled
0: Copy forbidden
1: Parameters copy 1
(voltage level and power rating are
totally same)
2: Parameters copy 2
(without considering voltage level
and power rating)
1
F639
Reserved
F640
Parameter copy type
0: Copy all parameters
1: Copy parameters
(except motor parameters from
F801 to F810/F844)
1
F641-
F649
Reserved
F650
High-frequency performance
Setting range:
0: Invalid
1: Terminal enabled
2: Enabled mode 1
3: Enabled mode 2
2
×〇
F651
Switchover frequency 1
F652-150.00
100.00
√〇
F652
Switchover frequency 2
0-F651
95.00
√〇
F653-
F670
Reserved
Timing Control and Protection: F700-F770
Function
Code
Function
Definition
Setting Range
Mfr’s Value
Change
F700
Selection of terminal free stop mode
0: Immediate free stop (coast stop)
1: Delayed free stop (coast stop)
0
F701
Delay time for free stop and programmable
terminal action
0.060.0s
0.0
F702
Fan control mode
0: Controlled by temperature
1: Running when inverter is powered on
2: Controlled by running status
2
F703
Reserved
F704
Inverter Overload pre-alarm Setpoint (%)
50~100
80
F705
Motor Overload pre-alarm Setpoint (%)
50~100
80