Introduction
22 (109) 192-011006N8 2019-07 09.10.19 09:27
The devices must be appropriately protected (e.g. by a switching cabinet). - Open
type equipment.
Use 60/75°C wires only
Use Copper Conductors Only
Do only use the Parker cables available under Accessories (see page 81) or
assemble the cables according to the specified regulations.
Control voltage supply (24 VDC) only permissible with "class 2" power supply.
Grounding Terminals - the screw terminals are suitable for Field Wiring
Connection only when the wire is provided with Eyelet Tube Terminal.
Overvoltage category III.
Short circuit ratings SCCR = 5000 Arms
The drive modules are equipped with a current limit. Values for maximum device
current and maximum motor current can be set via PSD ServoManager (Chapter
resp. Menu Limit values & Motor Characteristics).
Integral motor overload protection is not available.
The drive does not incorporate internal overload protection for the motor load and
this overload protection shall be provided in the end use applications.
Motor over temperature sensing is not provided by the drive
Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the
Manufacturer Instructions, National Electrical Code and any additional local
codes
Suitable for use on a circuit capable of delivering not more than 5000 rms
Symmetrical Amperes, 240 Vac maximum. When protected by Listed Cartridge
Fuses, Non-Renewable (JDDZ), Time-Delay Class-CC Fuses, rated 600 Vac, 3 A
or 8A (for model No. PSD1SW1200) / 6 A or 12A (for model No.
PSD1SW1300). See table below for the manufacturers, model number and
electrical ratings.
External Branch Circuit Protection
Device
Spezification
Time-Delay "Class-CC" Fuses
Listed Cartridge Fuses, Non-Renewable manufactured by
Cooper Bussmann LLC (E4273)
(200 kARMS Symmetrical A.I.C.)
Model No.
Current [Arms]
Voltage [VAC]
Quantity Phase
PSD1-S_1200
LP-CC-8
8
600 1 phase
LP-CC-3
3
600 3 phases
PSD1-S_1300
LP-CC-12
12
600
1 phase
LP-CC-6
6
600 3 phases
Alternate External Branch Circuit Protection
Device
Spezification
Time-Delay "Class-CC" Fuses
Listed Cartridge Fuses, Non-Renewable manufactured by
Mersen USA Newburyport-MA LLC (E2137)
(200 kARMS Symmetrical A.I.C.)
Model No.
Current [Arms]
Voltage [VAC]
Quantity Phase
PSD1-S_1200
ATDR8
8
600
1 phase
ATDR3
3
600
3 phases
PSD1-S_1300
ATDR12
12
600 1 phase
ATDR6
6
600
3 phases
For use in Canada:
External Surge Protection devices (required in the end use instalation) -
According to the Canadian Standard C22.2-No.274-13.
R/C Surge-Protective Device (VZCA2/8) and CSA-Certified transient surge
suppression shall be installed on the line side of this equipment and shall be