EasyManua.ls Logo

Parker TPDM - Type 2 Phasing

Parker TPDM
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parker Hannifin Manufacturing Srl user’s manual TPDM
51
6.6.2 Type 2 phasing
b94.4 actives this procedure. The parameters are shown in the table below:
Par. Description Field/Unit Def
Type/
Notes
Pr196 To insert number of the step to turn encoder ±32767 1024
R/W
M
b94.4
Command phasing 2. It’s necessary to disable the
software (b40.9=0); enable the hardware
(b41.5=1), and driver OK (Pr23=0).
The motor executes a vibration, the standing
depends to the type of the motor and to the load.
0
Pr89
Status:
0 if positive result
2 if wrong enabling
5 if drive not ready (Pr230 or open inrush)
6 Pr201 parameter calculated (frequency of
vibration) is different of 25 unit from starting value
7 Pr201 parameter calculated (frequency of
vibration) exceeds 200 unit (max. value)
R
b41.6
Phasing result =1 if positive result of the procedure
and necessary condition for drive OK (b41.4)
0
R
The calculated value of Pr201 at the end of the procedure, if it is save, it permits at the new
start-up that the procedure starts from this value, and if the mechanical conditions don’t change,
is made only one vibration of standing fixed by Pr201.
N.B.:(*) during the phasing procedure the motor must be motionless, so if the motor is on vertical
axe, this system must be motionless without to use the brake.
(**) the encoder simulation can’t use zero encoder track as reference for reset the machine, when the
system uses an axis control and the FBK is an incremental encoder.

Table of Contents

Related product manuals