SD700
POWER ELECTRONICS
20
DESCRIPTION OF PROGRAMMING PARAMETERS
Parameter /
Default Value
Name /
Description
Range
Function
Set on
RUN
5 INITIALISE=0
G1.5 / Parameter
initialize
0 5
It allows selection of the parameters that we desire to initialize back to the factory
default value.
OPT.
DESCRIPTION
FUNCTION
0
NO INIT
None of parameters is initialized.
1
USR PRMTR
User parameters are only
initialized.
2
MTR PRMTR
Motor data are only initialized.
3
ALL PRMTR
All parameters of the drive are
initialized.
4
INIT_SOFT
Newly added parameter values
are initialized.
5
INIT_PARTIAL
All parameters of the drive are
initialized except communication
parameters.
NO
6 SHORTmenu=NO
G1.6 / To hide
some
configuration
menus
NO
YES
If it is active, then configuration menus will not be accessible. Only visible G1
OPTIONS MENU, G10 LIMITS, and Display groups.
NO
7 PROG= STANDARD
G1.7 / Program
activation
STANDARD
PUMP
MACRO for
VYSTA
programs
It allows selection additional functionalities. If PUMP is selected, then extended
functionality for pumping control G25 will appear as available.
The group G25 will be hidden if the pump program is not active. Furthermore,
there are not available any configuration options related to pump control included
in other parameters.
Once selected the pump program, a character will appear in the upper line of the
display, beside the drive status, indicating constantly that the pump program is
active. The letter “b” in Spanish and the letter “p” for English / German.
The most of parameters relative to the pump control are located in Group 25,
excepting those setting relatives to inputs and outputs that can be found in groups
G4 and G7.
Additionally there are some visualization screens included in visualization groups
SV.5 and SV.8.
For additional information, see the ‘Pump Application Manual’ for the SD700.
NO
SV 1.8 Visual
The programming line becomes a visualization line.
11 FAN CTRL=RUN
G1.11 / Drive fan
control mode
RUN
TEMP
FIX
It allows selecting the operation mode for drive fans.
OPTION
FUNCTION
RUN
The fans of the drive are connected with the start
command and they are disconnected after 3
minutes once the drive is stopped.
TEMP
The fans are connected at 51ºC and they are
disconnected when temperature is below 47ºC.
FIX
Starts the fans when the drive is not in external
supply mode.
YES
12 RECT.BRIDGE=0
G1.12 / Amount
of pulses of
rectifier bridge
0 to 3
It allows setting the amount of pulses of the rectifier bridge at the drive input.
OPT.
DESCRIPTION
0
6 PULSES
1
12 PULSES
2
18 PULSES
3
24 PULSES
NO
14 SER GRP PWD =
OFF
Group reserved for the technical service and qualified personnel of Power Electronics

Table of Contents

Other manuals for Power Electronics SD700 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Power Electronics SD700 Series and is the answer not in the manual?

Power Electronics SD700 Series Specifications

General IconGeneral
BrandPower Electronics
ModelSD700 Series
CategoryInverter
LanguageEnglish

Related product manuals