DESCRIPTION OF PROGRAMMING PARAMETERS
39
4.8.2. Subgroup 8.2 S8.2: Analogue Outputs
Parameter /
Default Value
Name /
Description
Range
Function
Set on
RUN
1 ANLG OUT1=01
G8.2.1 / Mode
selection for
Analogue Output
1
00 27
Analogue output is programmable according to the following table:
OPT
DESCR.
FUNCTION
UNITS
00
NONE
It is not used.
-
01
SPEED
MOTOR
Signal proportional to
the motor speed.
% Motor speed
02
CURRENT
MOTOR
Signal proportional to
the motor current.
% Motor rated
current
03
VOLTAGE
MOTOR
Signal proportional to
the motor voltage.
% Motor rated
voltage
04
POWER
MOTOR
Signal proportional to
the motor power.
% Motor power
05
TORQUE
MOTOR
Signal proportional to
the motor torque.
% Motor torque
06
PF MOTOR
Signal proportional to
the motor power factor.
% Motor rated
Cosine Phi
07
TEMP
MOTOR
Signal proportional to
the motor temperature.
% Motor
temperature
08
FREQUENCY
IN
Signal proportional to
the input frequency.
% Input
frequency
(50Hz=100%)
09
INPUT
VOLTAGE
Signal proportional to
the input voltage.
% Equipment
rated voltage
10
DC BUS
Signal proportional to
the DC Bus voltage.
% Motor voltage
x 1.414
11
DRIVE TEMP
Signal proportional to
the drive temperature.
% Drive
temperature
12
SPEED REF
Signal proportional to
the speed reference.
% Motor speed
13
Reserved
Reserved for future
use.
14
PID
REFERENCE
Signal proportional to
the reference in PID
mode.
%
15
PID
FEEDBACK
Signal proportional to
the feedback in PID
mode.
%
16
PID ERROR
Signal proportional to
the error (difference
between reference and
feedback) in PID mode.
%
17
ANLG INPUT
1
Analogue input 1 signal
is transferred to
analogue output.
%
18
ANLG INPUT
2
Analogue input 2 signal
is transferred to
analogue output.
%
19
ANLG
INPUT1+2
The average of the
analog inputs 1 and 2.
%
20
CURRENT
FLOW
Analogue signal
proportional to the read
flow through analogue
input or pulse input.
%
21
MAX SCALE
It forces the output to
maximum value.
100% bottom
scale
22
ABSOLUT
SPEED
Signal proportional to
the motor speed without
sign (absolute value).
% Motor speed
23
ABSOLUT
TORQUE
Signal proportional to
the motor torque
without sign (absolute
value).
% Motor torque
24
ENCODER
SPD
Signal proportional to
the real speed of the
encoder
% rpm (motor
nameplate)
NO
NO
2 FORMT 1=4-20 mA
G8.2.2 / Format
selection for
Analogue Output
1
0-10V
±10V
0-20mA
4-20mA
Analogue output 1 is programmable in one of four possible formats according to
the system requirements.
NO

Table of Contents

Other manuals for Power Electronics SD700 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Power Electronics SD700 Series and is the answer not in the manual?

Power Electronics SD700 Series Specifications

General IconGeneral
BrandPower Electronics
ModelSD700 Series
CategoryInverter
LanguageEnglish

Related product manuals