SD700
POWER ELECTRONICS
38
DESCRIPTION OF PROGRAMMING PARAMETERS
Parameter /
Default Value
Name /
Description
Range
Function
Set on
RUN
12 INVERT REL3=N
G8.1.12 / Relay
3 inversion
N
Y
It allows user to invert the logic of relay 3 functionality.
Relay 3 has one normally open contact (connection 32/33) and another normally
close contact (connection 33/34).
OPT
FUNCTION
N=NO
No inversion.
Y=YES
Inversion of relay logical function.
NO
13 CRAspdOF=+5.0%
CRANE BRKoff SPD
G8.1.13 / Speed
for disconnecting
relay in option
Crane
+0.0% to
+250%
This parameter allows setting the speed below which, any relay configured with
option ‘32 CRANE BRAKE’ will be deactivated.
YES
34 Dig Out FB = DO1
G8.1.34 / Digital
Output Feedback
DO1
DO2
DO3
This parameter allows setting the digital output that will be associated to the
feedback functionality. When the digital input option “Dig Output FB” is set, its
functionality is associated to the digital output set in this parameter. If the time
between the activation of the digital output and the digital input exceeds the time
adjusted in the parameter “G8.1.35 DlyDoFB”, the drive trips by fault F55.
YES
35 DlyDoFB = 1.0s
G8.1.35 / Delay
Digital Output
Feedback
0.5 to 60.0s
It allows setting the maximum time that the digital input configured as “Dig Output
FB” will wait the feedback of the digital output set in G8.1.34 before tripping the
drive by fault 55.
YES
36 FAULT1 = OFF
G8.1.36 /
Closure of digital
output “FAULT1”
0 - 90
It allows setting the fault (OFF, F1, F2..., F90) which will close the digital input
configured as FAULT1, FAULT2, FAULT3 and FAULT4.
OPT
DESCRIPTION
0
OFF
1
F1
....
...
90
F90
YES
37 FAULT2 = OFF
G8.1.37 /
Closure of digital
output “FAULT2”
0 - 90
38 FAULT3 = OFF
G8.1.38 /
Closure of digital
output “FAULT3”
0 - 90
39 FAULT4 = OFF
G8.1.39 /
Closure of digital
output “FAULT4”
0 - 90

Table of Contents

Other manuals for Power Electronics SD700 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Power Electronics SD700 Series and is the answer not in the manual?

Power Electronics SD700 Series Specifications

General IconGeneral
BrandPower Electronics
ModelSD700 Series
CategoryInverter
LanguageEnglish

Related product manuals