24.
the
Remote
EPO
feature opens all breakers and and contactors in theUPS
cabinet and isolates power from
your
@Ml
!oad.
Local electrical codes may
also require tripping upstream protective devrces to the UPS.
25.
Your UPS equipment’s operating environment must meet the size and weight
requirements shown in Table S. according t0 your UPS system configuration:
26.
The basic environmental requirements for operation
of
the UPS system are:
Ambient Temperature Range:
1 O-40’ C (50
-
104’
F)
Recommended
Opexatfng
Range:
20-25’
C
(G
-
77’
F)
Maximum Relatfve Humidity: 95%
DEscRIpTIoN:
INSTALIATION
NOlES
ORAWING
ND:
164200253-l
ISHEET:
60,(
CREATEDBY:
L
0RlANw
REVWOH
AILb4E:
8-24-4

Table of Contents